Oil and Gas Wiring Conduits
Anamet Electrical offers several lines of Anaconda SEALTITE® suitable for the extreme environments associated with the petrochemical industry.
• HTUA: Special PVC cover, Temperature range -51°F to +221°F (-46°C to +105°C)
• HCX: Extreme temperature jacket, Temperature range -76°F to +302°F (-60°C to +150°C)
• EFL: Lightweight corrosion resistant aluminum core, Temperature range -4°F to +140°F (-20°C to +60°C)
• ZHUA: Special Zero Halogen cover, Temperature range -40°F to +176°F (-40°C to +80°C)
• OR: Special Oil Resistant PVC cover, Temperature range -9°F to +221°F (-23°C to +105°C)
Type HTUA
UL Listed, CSA Certified Higher and Lower Temperatures Liquid Tight Flexible Metal Conduit (LFMC) Construction
• Constructed of continuously interlocked hot dipped zinc galvanized steel core for exceptional crush and corrosion resistance.
• Durable, sunlight resistant and flame retardant thermoplastic PVC jacket that resists heat, oil and chemical breakdown.
• Designed for most extreme temperature applications.
NEC Articles
• Article 250.118 (6) Equipment Grounding
• Article 300.22 (D) Information Technology Equipment
• Article 350 Liquid-Tight Flexible Metal Conduit (LFMC)
• Article 501.10 (B) (2) Class I Div. 2
• Article 502.10 (A) (2) and (B) (2) Class II Div. 1 2
• Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
• Article 620.21 Elevator Wiring Methods
• Article 645.5 (E) (2) Under Raised Floors
Installation
• Conduit used with standard liquid-tight
connector for easy installation.
IP 66/67 Rated when installed with approved connectors.
• Approved for both exposed and concealed locations Rated for temperature ranges UL temps -51°F to + 221°F (-46°C to +105°C), CSA -51°F to 167°F (-46°C
to +75°C).
• Approved as an equipment grounding conductor in sizes 3/8" through 1-1/4" if the total grounding path is 6 ft. or less and the circuit conductors are protected by over 20 amps for 3/8" and 1/2" and 60 amps or less for 3/4" through 1-1/4".
• Suitable for use in hazardous locations per NEC Articles 501 Class I Div. 2, Article 502 Class II Div. 1 & 2, Article 503 Class III Div. 1 & 2.
• Manufactured in a full range of trade sizes from 3/8" through 4".
• Approved for direct burial and in concrete trade sizes 3/8" through 4".
• Complies with UL Standard 360 File No. E18917; CSA C22.2 File No. 158897; and NEC Article 350.
Type HCX
Extreme Temperature Jacket Liquid Tight Flexible Metal Conduit (LFMC) Construction
• Constructed of continuously interlocked hot dipped zinc galvanized steel core for exceptional crush and corrosion resistance.
• Durable, sunlight resistant thermoplastic rubber jacket that resists heat, oil and chemical breakdown.
Installation
• Conduit used with standard liquid-tight connector for easy installation. IP 66/67 Rated when installed with approved connectors.
• Delivers superior wiring protection where agency approvals are not required.
• Manufactured in a full range of trade sizes from 3/8" through 4".
• Smooth appearing jacket for exposed applications.
• Rated for temperature range of -76¢ªF to +302¢ªF (-60¢ªC to +150¢ªC).
• Provides liquid-tight raceway for electrical conductors
Type ZHUA
Zero Halogen, Low Smoke, Low Flame Spread UL Listed Liquid Tight Flexible Metal Conduit
Construction
• Constructed of continuously interlocked hot dipped zinc galvanized steel core for exceptional crush and corrosion resistance.
• Durable, sunlight resistant, flame retardant, LOW SMOKE and ZERO HALOGEN TPU jacket that resists heat, oil and chemical breakdown.
• Designed for most extreme temperature applications.
• Meets the demands of today’s higher temperature rated conductors.
MEETS or EXCEEDS the following STANDARDS
• Flame Spread Index ASTM E162
• Smoke Density (Generation) ASTM E662
• Toxic Gas Generation Bombardier BSS 7239
• Jacket Material is U.L. 94 Certified
• Conduit is U.L. 360 Listed
NEC Articles
• Article 250.118 (6) Equipment Grounding
• Article 300.22 (D) Information Technology Equipment
• Article 350 Liquid-Tight Flexible Metal Conduit (LFMC)
• Article 501.10 (B) (2) Class I Div. 2
• Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
• Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
• Article 620.21 Elevator Wiring Methods
• Article 645.5 (E) (2) Under Raised Floors
Installation
• Conduit used with standard liquid-tight connector for easy installation. IP 66/67 Rated when installed with approved connectors.
• Approved for both exposed and concealed locations. Rated for temperature ranges -40°F to + 176°F (-40°C to +80°C).
• Approved as an equipment grounding conductor in sizes 3/8" through 1-1/4" if the total grounding path is 6 ft. or less and the circuit conductors are protected by over 20 amps for 3/8" and 1/2" and 60 amps or less for 3/4" through 1-1/4".
• Suitable for use in hazardous locations per NEC Article 501 Class I Div. 2, Article 502 Class II Div. 1 & 2, Article 503 Class III Div. 1 & 2.
• Manufactured in a full range of sizes from 3/8" through 4".
• Approved for direct burial and in concrete trade sizes 3/8" through 4".
• All Sizes Comply with UL Standard 360 File No. E18917; and Trade sizes 1/2" and 3/4" are CUL Listed.
Type EFL
Aluminum Core Light Weight Liquid Tight Flexible Metal Conduit (LFMC)
Construction
• Constructed of continuously interlocked aluminum core for exceptional crush and corrosion resistance.
• Durable, sunlight resistant thermoplastic PVC jacket that resists heat, oil and chemical breakdown.applications.
• Meets the demands of today’s higher temperature rated conductors.
Installation
• Conduit used with standard liquid-tight connector for easy installation. IP 66/67 Rated when installed with approved connectors.
• Delivers superior wiring protection where agency approvals are not required.
• Manufactured in a full range of trade sizes from 3/8" through 4".
• Smooth appearing jacket for exposed applications.
• Rated for temperature range of -4¢ªF to +140¢ªF (-20¢ªC to +60¢ªC).
• Provides liquid-tight raceway for electrical conductors.
Type OR
Special Oil Resistant Jacket Liquid Tight Flexible Metal Conduit (LFMC)
Construction
• Constructed of continuously interlocked hot dipped zinc galvanized steel core for exceptional crush and corrosion resistance.
• Durable, sunlight resistant thermoplastic PVC jacket that resists heat, oil and chemical breakdown.
Installation
• Conduit used with standard liquid-tight connector for easy installation. IP 66/67 Rated when installed with approved connectors.
• Delivers superior wiring protection where agency approvals are not required.
• Manufactured in a full range of trade sizes from 3/8" through 4".
• Smooth appearing jacket for exposed applications.
• Rated for temperature range of -9¢ªF to +221¢ªF (-23¢ªC to +105¢ªC).
• Provides liquid-tight raceway for electrical conductors.
STAINLESS STEEL CONNECTORS AVAILABLE IN 3/8" -1" STRAIGHT AND 90°
Construction
• Stainless Steel Type 304 connector, has a four piece construction consisting of a gland nut, sealing ring, high tensile grounding cone and body.
• Designed with an insulated throat to prevent wire damage during installation.
• Included sealing ring and stainless steel lock nut provides a means for connecting the fitting to boxes.
• Excellent corrosion resistance, strength and durability.
Installation
• Connector is ideal for use with standard liquid-tight conduit to allow easy installation. IP 66/67 Rated when installed with approved conduit.
• Approved for both exposed and concealed locations. Rated for temperature ranges -49ºF to + 221ºF (-45ºC
to +105ºC).
• Suitable for harsh industrial, food and beverage, petrochemical, waste water, salt water and other corrosive applications
• Suitable for use in hazardous locations per NEC Articles 501 Class I Div. 2, Article 502 Class II
Div. 1 & 2, Article 503 Class III Div. 1 & 2.
• Manufactured in a range of trade sizes from 3/8" through 1".
• Complies with UL Standard 514B and CSA C22.2 combined File No. E234207