Turning Point Analysis with dataTaker Data Loggers

Print | 
Email |  Comment   Share  

Turning Point Analysis with dataTaker Data Loggers
Turning Point Analysis with dataTaker Data Loggers
Click Here to Enlarge Picture

(Archive News Story - Products mentioned in this Archive News Story may or may not be available from the manufacturer.)

CAS DataLoggers
12628 Chillicothe Rd., Unit J
Chesterland, OH, 44026
USA



Press release date: September 13, 2012

Flexible dataTaker Systems Let You Monitor Almost Any Value

CHESTERLAND OH - Turning Point Analysis is a method of data compression for arbitrary waveforms. The incoming waveform is sampled at speed and analyzed in real time to identify the turning points (Maxima and Minima) of the waveform, and the value and time of the turning point are also logged to memory for later recovery. The Applications Specialists at CAS DataLoggers have put together this tutorial to examine this subject in detail, including a simple method of noise rejection (dead banding) for dataTaker DT800 and DT500 data loggers.

Applications:
Turning Point Analysis can be used in a large number of applications where a waveform needs to be monitored. Typical examples include but are not limited to:
Cyclic fatigue monitoring of structures
Wave height monitoring of coastal structures / shore erosion
Tank level monitoring
Air condition monitoring
Pressure fluctuations in pipes
Temperature controller monitoring

Algorithm:
The incoming waveform is sampled and the current data point (n) is compared with the previous data point (n-1). If the difference between the two samples is positive, then the signal is rising (a=1), and if negative, then the signal is falling (a=-1).

By comparing the difference of a-1 to a when the signal is rising or falling, a-1 - a = 0. At the next reading after a maxima turning point, the difference of a-1 - a = 2 and for a minima a-1 - 2 = -2, thus not only giving a clear indication of n-1 being a turning point but also indicating if a maxima or minima. This technique can also be applied to drawing an envelope around a waveform.

If n > n-1 then a = 1 (Indicates a rising signal)
If n < n-1 then a = -1 (Indicates a falling signal)
If (a-1)-a < 0 > then n-1 is a valid turning point
In the dataTaker data logger code, this is represented by the command lines:

1CV(DF,=5CV,W)
6CV(DF,=6CV,W)=-1x(5CV<0)+(5CV>0)

The amount of data compression is the ratio of the twice the signal frequency to the sample rate. I.e. for a 2 Hz signal and 200 Hz sample rate, the compression ratio is 200 / (2x2) = 50:1. This has a great impact on storage capacity, data efficiency and maximum sampling duration.

Noise Rejection:
The turning point algorithm is very sensitive and is quite capable of extracting white noise on a system as actual turning points. This is particularly noticeable when there is a very low frequency or static signal.

To reduce the extraction of noise as turning points, a dead band is applied around the last valid turning point. If a turning point is detected that has a value inside the range of the last valid turning point +/- the noise rejection level, then that point is rejected. If the value is outside the range, then the data point is considered to be valid and is recorded.

While this noise rejection method is simple and effective in most cases, it does occasionally pick up interim points as turning points. These interim points can be easily identified and removed in post-processing. Other noise rejection routines will be evaluated and may be included at a later stage.

DT800 Code:
BEGIN"TP"

Turning Point Analysis Routine for DT800
This code logs the turning points of any waveform.
The time of turning is recorded logged in 4CV.

Notes: 4CV holds the time since midnight in seconds,
this limits the time accuracy to 2 decimal places.

Known Issues:
The noise reduction is primitive and in some instances
will record false turning points.
These only happens on occasion and these points can be removed by post processing.

7CV(W)=10 '7CV hold the dead band for noise rejection
Any turning points less that the current turning point +/- 7CV will be rejected.
8..9CV(W)=0
Minimum noise level and Maximum noise level respectively.
10CV(W)=0
Holds last turning point. Used for noise rejection.

Schedule A is where the turning points are actually logged.
Note: The X schedule must be before the fast schedule.

RAX LOGONA
2CV("TP ~mV",FF7)
4CV("Time ~Sec",FF7)

Schedule B detects the turning point

RB,FAST
2CV(W)=1CV Shift register for reading
4CV(W)=3CV Shift register for time
1V(=1CV,GL20V,W) Read Current value (Note: Gain lock to suit)
T(=3CV,W) Read current time
1CV(DF,=5CV,W) Read difference between readings

This Boolean in the next bit of code returns 1 if the current reading is greater than the last (Rising 'signal) and returns -1 if the current reading is less than the last (Falling signal)
By taking the difference (DF) 6CV holds 2 for a maxima turning point or -2 for a minima turning point.
6CV(DF,=6CV,W)=-1x(5CV<0)+(5CV>0)
Calculate Lower noise tolerance.
8CV(W)=10CV-7CV
Calculate Upper noise tolerance.
9CV(W)=10CV+7CV
Then check for turning point and noise then save turning point if valid.
IF(6CV<>-0.5,0.5)AND If a turning point AND
IF(1CV<>8CV,9CV){[10CV=2CV XA]} If the current signal is outside the noise dead band THEN
Record new turning point and Log turning point data
END
TN-0015-A0 Page 5 of 6 19 February 2004

DT500 Code:
BEGIN

Turning Point Analysis Routine for DT500
This code logs the turning points of any waveform.
The time of turning is recorded logged in 4CV.
Notes: 4CV holds the time since midnight in seconds,
this limits the time accuracy to 2 decimal places.

Known Issues:
The noise reduction is primitive and in some instances will record false turning points.
These only happens on occasion and these points can be removed by post processing.

7CV(W)=10 7CV hold the dead band for noise rejection
Any turning points less that the current turning point +/- 7CV will be rejected.
8..9CV(W)=0 Minimum noise level and Maximum noise level respectively.
10CV(W)=0 Holds last turning point. Used for noise rejection.

Schedule A detects the turning point

RA
2CV(W)=1CV Shift register for reading
4CV(W)=3CV Shift register for time
1V(=1CV,GL20V,W) Read Current value (Note: Gain lock to suit)
T(=3CV,W) Read current time
1CV(DF,=5CV,W) Read difference between readings
This Boolean in the next bit of code returns 1 if the current reading is greater than the last
(Rising signal) and returns -1 if the current reading is less than the last (Falling signal)
By taking the difference (DF) 6CV holds 2 for a maxima turning point or -2 for a minima turning point. 6CV(DF,=6CV,W)=-1x(5CV<0)+(5CV>0)
Calculate Lower noise tolerance.
8CV(W)=10CV-7CV
Calculate Upper noise tolerance.
9CV(W)=10CV+7CV
Record turning point data
RX LOGONX
2CV("TP",FF5)
4CV("Time",FF5)
RZ
Then check for turning point and noise then save turning point if valid.
ALARM1(6CV<>-0.5,0.5)AND If a turning point AND ALARM2(1CV<>8CV,9CV)"[10CV=2CV X]" If the current signal is outside the noise dead
band THEN Record new turning point and Log
turning point data
END

For more information on the new Series 3 dataTaker dataloggers which measure nearly any physical value, or to find the ideal solution for your application-specific needs, contact a CAS Data Logger Applications Specialist at (800) 956-4437 or visit the website at www.DataLoggerInc.com.

Contact Information:
CAS DataLoggers, Inc.
12628 Chillicothe Road
Chesterland, Ohio 44026
(440) 729-2570
(800) 956-4437
sales@dataloggerinc.com
www.dataloggerinc.com
Print | 
Email |  Comment   Share  
Contacts: View detailed contact information.


 

Post a comment about this story

Name:
E-mail:
(your e-mail address will not be posted)
Comment title:
Comment:
To submit comment, enter the security code shown below and press 'Post Comment'.
 



 See related product stories
More .....
 See more product news in:
Test and Measuring Instruments
 More New Product News from this company:
Thermistor Probe suits medical monitoring applications.
Data Acquisition System provides machine fault diagnostics.
Remote Temperature Recording Kit verifies thermal sterilization.
Data Acquisition System targets universities and research.
Temperature and Humidity Data Logger features graphic screen.
More ....
| Featured Manufacturing Jobs
 Other News from this company:
Recording Closed-Loop Control System Cycles for HVAC Savings
CAS DataLoggers is Attending CSIA 2014
Vaccine Safety: What's It Worth?
CAS DataLoggers Hires New Applications Specialist
Test and Monitoring for Automatic Car Seats
More ....
 Tools for you
Watch Company 
View Company Profile
Company web site
More news from this company
E-mail this story to a friend
Save Story
Search for suppliers of
Data Loggers & Data Logging Equipment
Join the forum discussion at: