Temperature Transmitters include RTD sensor.

Press Release Summary:



Series PRTXD provides 4-20 mA output signal representing temperature. When held, front panel TEST button sets loop current and display to test calibration level, independent of temperature input, allowing testing of system operation. Featuring NEMA 4X rated housing, units include 3½ digit LCD with ½ in. digit height and display update rate of 3 readings per second. Spring-loaded probes are available for use with thermowells.



Original Press Release:



Temperature Transmitter with Display and RTD Sensor  PRTXD Series



Two-Wire Transmitter
4 to 20 mA Output
3-1/2 Digit Display
RTD Probe Included
NEMA 4X (IP66) Housing

The PRTXD Series are two-wire transmitters that provide a 4 to 20 mA signal representing temperature. The units include a 3-1/2 digit display and RTD sensor. The NEMA 4X (IP66) housing protects the electronics. Units are available with spring-loaded probes for use with thermowells.

Controls -- Non-interactive zero and span, ±10% range,Test calibration level; 0 to100% range

Display: 3-1/2 digit LCD, 1/2" digit height, 3 readings per second nominal display update rate

Sensor: 100 . RTD element, 0.00385 alpha coefficient IEC-751 Class B: ±0.3°C at 0°C, ±1.1°C at 150°C

Test Function: Front panel TEST button when held, sets loop current and display to test calibration level, independent of temperature input, to allow testing of system operation.

1/2" NPT male hex nipple, 316 stainless steel probe sheath

For More Information, please contact OMEGA Engineering, Inc. at
203-359-1660 or go to: http://www.omega.com/Temperature/pdf/PRTXD.pdf