Reduce Ventilation Air Costs


The Customer is a manufacturer and supplier of coated and laminated films adhesive products. During the manufacture of their products different inks, adhesives and coatings are applied onto a wide variety of surfaces including films, non-woven, felts and rubbers. The solvents in these materials are evaporated off in a heating process. The company was looking to reduce ventilation air and fuel costs without affecting production rates or violating the NFPA safety directives. They were using large amounts of heated air to ventilate the dryers to keep the solvent vapor concentration below 25% LFL as directed by the NPFA codes.



Codes allow a substantial reduction in air in cases where a continuous solvent vapor analyzer is installed. When such instruments are installed to continuously sample the exhaust of a dryer zone, the vapor concentration in that zone is allowed to rise as high as 50% LFL.



The company chose to install PrevEx Flammability Analyzers on their dryers so they could run above 25%LFL. This allowed them to reduce costs while maintaining safety and production levels as well. They chose the PrevEx because they change their ink mix regularly and they did not want to have to recalibrate each time they did. With the “Universal Calibration” capability of the PrevEx, they don’t have to recalibrate when these changes occur. This allows them to continue production and avoid downtime associated with re-calibration. The PrevEx gives consistent and reliable readings with multiple or changing solvent concentrations. The analyzer features fast response, failsafe operation, low maintenance and easy servicing.



After this successful installation, the Company has been adding analyzers to their plants worldwide.



http://www.controlinstruments.com/documents/reduce-ventilation-air-costs



Visit our website to find out how we can help you select the safest, most efficient economical system for your application.



Reduce Ventilation Air Costs



New Case History from:

Control Instruments Corp.

25 Law Drive

Fairfield, NJ 07004

1-973-575-9114

www.controlinstruments.com

Contact This Company

All Topics