New Chiller Technology From McQuay Combined with Imaginative Renovation Creates Showplace for Cal State Campus


The expansive Acacia Court Building in Stockton, California, originally a state hospital built in the 1920s, has been given a new life. An extensive renovation has converted this 100-yard-long concrete building into a showplace of University Park, located in Stockton's historic Magnolia District. The Stockton Midtown neighborhood is being re-designed as a "live, learn, work, walk" re-development, and Acacia Court is home to the satellite campus of California State University, Stanislaus-Stockton. Students and staff occupy part of the first floor of the sprawling building; with future plans to include expansion into other sections as well. The renovation draws on unique technology, including an HVAC system designed around a new frictionless, magnetic bearing centrifugal chiller from McQuay-with impressive results. The chiller consumes far less power, costs less to operate, and generates much less noise than conventional chillers.

In 2002, The Grupe Commercial Company, a respected California developer, was awarded the University Park contract to develop the area into educational, office, retail and residential facilities, as well as a community center. Over 32 buildings have been razed; 19 will be renovated. Part of the goal is to keep floor plan changes to a minimum, primarily as a "renovate to suit" project.

Working with McQuay and its representative, Norman Wright Mechanical Equipment Corporation, The Grupe Commercial Company determined that the HVAC system was high on the list of systems to be updated at Acacia Court. The existing system included two chiller units dating from the 1950s, and some of the piping for them had collapsed. "The efficiency of the old system was really poor," said Chris Rasmussen of The Grupe Commercial Company's facility management department. "We explained to the university that the building needed a new chiller, along with new piping and a cooling tower."

A new kind of chiller for an old building

The McQuay frictionless chiller features magnetic bearing compressor technology that is oil-free. This design significantly reduces sound levels, because the magnetic bearings eliminate the metal-to-metal contact noise of conventional bearings. Sound pressure ratings are as low as 77 dBA per ARI Standard 575. Energy performance is also revolutionary. The McQuay frictionless centrifugal chiller operates as low as 0.375 kW/ton IPLV, the most efficient performance in its tonnage range in the industry. Full load performance is as low as 0.62 kW/ton-about 32 percent more efficient than screw compressor chillers.

"The magnetic bearing technology of the McQuay frictionless centrifugal chiller provides superior energy efficiency by eliminating the high friction losses of conventional centrifugal compressors," said Daryl Showalter, director of marketing, McQuay chiller products. "Variable frequency drives unload the chiller to 10 percent of full load. The chiller requires less than five amps to start, compared to 500 to 600 amps for a traditional screw compressor chiller. And, because magnetic bearings require no lubrication, there is no need for oil heaters, oil coolers, oil pumps or oil piping."

"A Really Good Experience"

Despite the completely new technology and design, installation went smoothly. "We had a really good experience," said Rasmussen. "We completed 90 percent of the installation work with our own maintenance staff, which really helped reduce the cost. And since the system went online, there has been zero unscheduled downtime because of problems, only scheduled downtime for a couple of software upgrades."

The two compressors of the frictionless chiller operate on a common refrigerant circuit, improving system reliability. In the event of a mechanical or electrical problem, one of the two compressors can continue to operate until repairs can be made. "If there is a problem with one compressor, we can still run with a 60 percent load on the other one," said Rasmussen.

The MicroTech II(TM) digital unit controller on the chiller effectively runs and monitors the chiller operation. The chiller is currently run based on a timeclock input because there are not as many maintenance issues with the magnetic bearing compressors. When the budget allows, the staff can integrate the MicroTech II chiller using BACnet®, LonTalk® or Modbus® protocol, thanks to the Protocol Selectability(TM) feature of the unit controller.

Saving on power, maintenance and cost
"As far as cost saving goes, it's just incredible," said Rasmussen. "The old chiller required 1,000 amps per leg at start-up. By contrast, when the new chiller starts up, each compressor takes only seven to 10 amps. Also, it ramps up more slowly, so we don't require a big surge of electricity in the beginning, which would be quite costly for the state."

Maintenance is equally worry-free. With the magnetic bearings compressors, the oil handling equipment of the chiller is eliminated. There is no need for oil pumps, oil reservoirs, oil coolers-and their associated maintenance costs-that are needed to maintain oil quality. The only requirement is to "punch tubes," or clean the pipes with a rotary brush, and blow out dust from the controls. "That's our PM (planned maintenance) for the chiller," said Rasmussen. "One other task we avoided is having to replace the refrigerant type in the near future." The McQuay frictionless chiller already uses HFC-134a refrigerant, which has no phase-out date.

Subtracting Noise

Noise is the other big plus with the frictionless chiller-or rather, lack thereof, since noise is virtually absent. "We have an air compressor in the basement, and when the air compressor is running, we can't tell if the chiller is also running," said Rasmussen. "We actually have to walk up to the unit to see if it's still going. We also have a couple of screw chillers at the university, and you can hear them all the way up from the basement to the first floor. They're totally different from the McQuay chiller."

For the university, the quiet new chiller makes the old building more useable as well as more efficient. While only a portion of the building is currently occupied, development plans include moving other university departments, as well as a computer lab, to Acacia Court.

Students and staff who use the building now and in the future will benefit not only from the renovated building and its technologically-advanced chiller, but also the entire "liveable" concept of the Magnolia District.

(For more information, see "Frictionless Compressor Chiller" at go.mcquay.com; and "Frictionless Chiller Compressor Technology," published in the January 2004 issue of HPAC Engineering, available at www.mcquay.com under frictionless chiller literature).

McQuay International delivers engineered, flexible solutions for commercial, industrial and institutional HVAC requirements with reliable products, knowledgeable applications expertise and responsive support. McQuay products and services are provided through a worldwide network of dedicated sales and service offices. For more information or the name of your local McQuay representative, call 1-800-432-1342 or visit www.mcquay.com.