Ferraz Shawmut Presents Arc Flash Research Findings


"Effect of Insulating Barriers in Arc Flash Testing"

Presented at PCIC Conference

NEWBURYPORT, MA, November 15, 2006 - Ferraz Shawmut, a global leader in the field of circuit protection, recently presented an insightful paper at the IEEE PCIC, the annual technical conference of the IEEE's Petroleum and Chemical Industry Committee, in Philadelphia, Pa.

Titled "Effect of Insulating Barriers in Arc Flash Testing," the paper documented Ferraz Shawmut's research findings regarding low-voltage arc flash testing using the standard IEEE 1584 test procedure, but with the electrode tips terminated in an insulating barrier instead of in the open air. This configuration is believed to be more representative of equipment in low-voltage industrial control panels and MCCs.

The paper, authored by R. Wilkins, M. Allison and M. Lang, describes arcing fault testing done in a high-power test laboratory with vertical conductors in a box, with the electrodes terminating in an insulating barrier. Testing components such as power distribution blocks, fuse holders and circuit breakers with the line-side arcing faults was compared to that of the barrier test. The insulating material, a solid 200mm x 27mm x 51mm block of glass-reinforced melamine, was selected for its ability to withstand high electromagnetic forces. High-speed video documented the differences in arc development with and without the barrier.

Some highlights of Ferraz Shawmut's research include:

o With the barrier in place the arc's downward development was redirected along the plane of the barrier, therefore, the high energy plasma flow went outward, toward the worker's expected location.

o Similar results could be observed when terminating vertical conductors in real industrial components.

o Tests yielded energy density measurements nearly twice those predicted by the IEEE 1584 equations when measured with copper calorimeters 18 inches from the electrode tips. They also produced shorter arc lengths, higher arcing currents and higher maximum incident energy density when compared with the standard arrangement.

o When the arcing fault was cleared by current-limiting fuses within the current-limiting range, there was no significant difference in energy density measurements compared to vertical testing.

o Arcing faults are more likely to be imbalanced on LV systems in today's power systems. This will require improved arc fault current prediction models.

o Arcing faults were easily sustained at 208V for available fault currents as low as 4.2kA.

o The effect of the barrier and the source X/R on arc sustainability was also studied.

o Vaporization of the copper electrode material was up to 60 percent higher than with other test configurations. High erosion of the copper electrodes directed a much larger quantity of copper spray toward the outside of the box.

o Combined with the pyrolysis of the insulating material, it is likely that this configuration creates more toxic smoke under similar electrical conditions.

As a result of this research, Ferraz Shawmut is recommending that the barrier test needs to be a consideration in the current standard vertical test arrangement. This would be in addition to a horizontal arrangement with open electrode tips pointing at the calorimeters. Based on Ferraz Shawmut's findings, adding an insulating barrier to the standard test set-up could be more advantageous, since the barrier allows sustained arcing at 208V. Ferraz Shawmut proposed that a similar arrangement be incorporated into future revisions of the IEEE 1584 testing standard.

For more information on arc flash testing, contact Ferraz Shawmut at info@ferrazshawmut.com, or download the complete paper as a PDF file from the Arc Flash Info Center at ferrazshawmut.com/arcflash

About Ferraz Shawmut

Ferraz Shawmut has been a leader in circuit protection for industry and the electrical market for more than 100 years. With a complete line of current-limiting fuses and accessories, Ferraz Shawmut prides itself on delivering innovative, problem-solving products like the SmartSpot® open-fuse indicator, Amp-Trap 2000® fuses, ULTRASAFE(TM) fuse holders, Protistor® semiconductor fuses and Select-A-Fuse® software. Two of the company's latest innovations are its new line of Amp-Trap® High-Speed Class J (HSJ) fuses, engineered specifically for the protection of today's sensitive electronic motor controllers, and the industry's first line of Finger-Safe Power Distribution Blocks (FSPDBs), delivering the ultimate in safety and ease-of-use when making power connections in electrical panels. Ferraz Shawmut, Inc. is a subsidiary of the Carbone Lorraine Group. For more information, contact the company by phone at (978) 462-6662 or visit www.ferrazshawmut.com